What are the types of grounding systems

Levi Zeigler July 23, 2019 0 comments

External Building Earth Ground System (BEGS) refers only to the method to externally ground a building. Normally is used in conjunction with a Single Point Ground System.

Halo Ground System (HGS) is a grounding philosophy dictating that all non-electrical metallic components have short lengths of bonding conductors from non-surge producing metallic objects to the Halo Ground System (HGS) for personnel safety purposes. A Halo Ground System (HGS) is sometimes called an Internal Ground Ring System. The Halo Ground System (HGS) was once widely used within radio equipment rooms.

The Halo Ground System (HGS) usually consists of a #2 AWG minimum, non-insulated, solid or stranded wire routed around the inside perimeter walls of a building or room. The Halo Ground System (HGS) is usually connected at each corner of the building or room to an external earth ground electrode system via a separate grounding electrode conductor.

Lightning Rod System (LRS) is a method of placing a metallic rod higher than a building to draw lightning to it and directing it to earth. This system is used in conjunction with an External Building Earth Ground System.

Multiple Point Ground System (MPGS) is sometimes called an Integrated Ground System (IGS). A Multiple Point Ground System (MPGS) is a grounding philosophy dictating that all major components of the Building Safety Protection System be designed and bonded to as many ground components as possible. These components consist of grounding electrode conductors, grounding conductors, grounded conductors, and incidental connections. These grounding conductors and incidental connections are designed to create multiple paths of resistance/impedance. This allows any voltage level that will be produced as current to flow or return to its source along these multiple paths. This should reduce personnel safety hazards and protect the equipment.

The grounding conductors and their grounded components do not require isolation from any incidental contact with other grounding conductors or grounded components. The more multiplicity and incidental point of contact among different grounding conductors and components within the Multiple Point Ground System (MPGS), the better, because circuit ground loops are thus created.

Single Point Ground System a Single Point Ground System (SPGS) is a grounding philosophy that requires all major components of the Building Safety Protection System to be designed and bonded to a single ground reference point. These components consist of ground electrodes, grounding electrode conductors, grounded conductors, and grounding conductors. These conductors are designed to create the path of least resistance/impedance. This allows any voltage produced as current to flow or return to its source along the proper designated path.

Carrying out the Single Point Ground System (SPGS) philosophy is simple yet very complex. The designated grounding conductors are methodically connected throughout the Building Safety Protection System within designated areas to the single ground reference point, the Master Ground Bar (MGB).

Grounding conductors and their grounded components must be isolated from any unintended contact with other grounding conductors and grounded components except at the single ground reference point, the Master Ground Bar (MGB). Any unintended points of contact among different grounding conductors and components create ground loops within the Single Point Ground System (SPGS) and are violations of the Single Point Ground System (SPGS).

The Single Point Ground System (SPGS) identifies each conductor on the ground bar by the type of conductor or the type of job the conductor is intended to do. The system is called the PANI system. The bar is divided up into sections and only one type to conductor is placed in that section of the ground bar. The following are some descriptions for conductors. Each conductor will then be placed within its proper section of the ground bar from left to right. Examples all the P's, all the A's, all the N's and then all the I's.

(P) - Surge Producers

  • Radio Frames
  • Telephone Cable Entrance Ground Bar (CEGB)
  • Telephone Cable Entrance Shields
  • Transformer Frame Inside Building
  • - Surge Absorber
  • AC Power Entrance Multi-Grounded Neutral (MGN)
  • Building Earth Ground System (BEGS)
  • Building Structural Steel (BSS)
  • Isolated AC Equipment Ground (ACEG)
  • Metallic Conduit System
  • Well Casing

(N) - Non-Isolated Ground Plane (NON-IGP) Equipment Grounds

  • Intra Office Cable Shield Bar (IOCSB)
  • Intra Office Cable Shields
  • Main Distribution Frame (MDF)
  • (-) Reference in a DC Power Plant with Negative Ground
  • (+) Reference in a DC Power Plant with Positive Ground
  • Storage Cabinets
  • Transmission Frames
  • Work Benches

(I) - Isolated Ground Plane (IGP) Equipment Grounds

  • Isolated Ground Plane AC Equipment Ground (ACEG)
  • Isolated Ground Plane Cable Runways
  • Isolated Ground Plane Frame Return Bar (IGP-FRB)
  • Isolated Ground Plane Logic Return Bar (IGP-LRB)
  • Isolated Ground Plane Metallic Conduit System

The Isolated Ground Plane Bar (IGPB) should be clearly stenciled or labeled and insulated from its support within the Isolated Ground Plane (IGP)


Post a Comment

Comments

    Post A Comment

    « Back to Blog


    Safety Protection Grid Solutions

    P.O. Box 1366
    Mansfield, OH 44901
    (855) 887-8463

     

    Qualify Us Now! ProView

     

    International Association for Radio Telecommunication Electromagnetics Logo

    NARTE Certified Engineer Logo

     

     

    NFPA Member Logo

    InterNACHI Logo

     

    Copyright © 2024 SPGS America. All rights reserved.