Or Call (855) 887-8463

Information Needed Before Selecting Any Ac Surge Protection Device(s) (SPDs) For Home or Facility.

Levi Zeigler August 24, 2022 0 comments

Over the years Underwriters Laboratories (UL) 1449, Institute of Electrical and Electronics Engineers (IEEE) standard C62.41, and International Electrotechnical Commission (IEC) 61643-1 surge protection terminology has been changing.

These changes and different marketing campaigns have added confusions when a layman needs to of select the correct Ac SPDs.

Example: No Nationally Recognized Testing Laboratory (NRTL) recognizes a Joule rating as an accurate rating of performance of Ac SPD. The acceptable is the kA rating per mode

Selecting the correct Ac SPDs involves more than just pricing. Ac SPDs needs to be chosen for the level of protection required for the equipment being protected. If not, then the Ac SPDs that are installed could be worthless from an equipment protection point of view.

Need To Know Terminology For Ac SPDs

  • Modes of Protection
  • Voltage Protection Rating (VPR)
  • Nominal Voltage
  • Maximum Continuous Operating Voltage (MCOV)
  • Nominal Discharge Current (In) Type 1 (10kA or 20kA)
  • Nominal Discharge Current (In) Type 2 (3kA, 5kA, 10kA or 20kA)
  • Nominal Discharge Current (In) Type 3

Note 1: IEEE Uses Categories instead of Types
Category C: Service Entrance, more severe environment: l0kV, l0kA surge
Category B: Downstream, ≥ 30' from category C, less severe environment: 6kV, 3kA surge
Category A: Further downstream, ≥ 60' from category C, least severe environment: 6kV, 0.5kA surge
Note 2: IEC Uses Type and Class instead of just Types
Type 1 / Class I / Class B
Type 1+2 / Class I+II / Class B+CType 2 / Class II / Class C
Type 2+3 / Class II+III / Class C+DType 3 / Class III / Class D

  • Ac Surge Protection Devices (SPDs) kA Protection Rating per Mode

Terminology Content For Ac SPDs

Modes Of Protection: Every Ac SPD made does not have each mode of protection protected.

  1. With Ac three phase you can purchase surge protection with up to 10 modes of protection.
    1. Phase A (L1) to Neutral
    2. Phase B (L2) to Neutral
    3. Phase C (L3) to Neutral
    4. Phase A (L1) to Ground
    5. Phase B (L2) to Ground
    6. Phase C (L3) to Ground
    7. Neutral to Ground
    8. Phase A (L1) to Phase B (L2)
    9. Phase A (L1) to Phase C (L3)
    10. Phase B (L2) to Phase C (L3)
  2. With Ac single phase you can purchase surge protection with up to 6 modes of protection.
    1. Phase A (L1) to Neutral
    2. Phase B (L2) to Neutral
    3. Phase A (L1) to Ground
    4. Phase B (L2) to Ground
    5. Neutral to Ground
    6. Phase A (L1) to Phase B (L2)

Voltage Protection Rating (VPR): The VPR is the voltage value where the Ac SPD limits a specific surge between modes of protection. The lower the VPR the better the equipment is protected

  1. UL 1449 has established Ac Surge Protection (SPDs) Voltage Protective Ratings (VPR) so that a consumer can purchase the per mode level of protection they desire.

When the SPD test results are:

The SPD VPR is:

330 Volts ≤ 330

330 Volts

331 Volts ≤ 400

400 Volts

401 Volts ≤ 500

500 Volts

501 Volts ≤ 600

600 Volts

601 Volts ≤ 700

700 Volts

701 Volts ≤ 800

800 Volts

801 Volts ≤ 900

900 Volts

901 Volts ≤ 1000

1000 Volts

1001 Volts ≤ 1200

1200 Volts

1201 Volts ≤ 1500

1500 Volts

1501 Volts ≤ 1800

1800 Volts

1801 Volts ≤ 2000

2000 Volts

2001 Volts ≤ 2500

2500 Volts

2501 Volts ≤ 3000

3000 Volts

3001 Volts ≤ 4000

4000 Volts

4001 Volts ≤ 5000

5000 Volts

5000 Volts ≤ 6000

6000 Volts

Per UL 1449 standard each Ac SPD VPR is established from the test results using only a 6” lead.

Depending on the voltage level, the rise time of the voltage, and the frequency of the voltage each foot of cable past the 6” lead length could add between 100-200 volts per foot above the UL VPR of the Ac SPD.
Example: customer purchases an Ac SPD with a 330 VPR but the Ac SPD lead length is 36”. This means during a power surge the 330 VPR rated Ac SPD could turn out to actually have a 600 to 900 VPR. See chart below for equipment damaged time from a quick voltage surge.

Quick Surge Duration Time and PEAK Voltages That Will Result in Equipment Damage

Line Voltage (RMS/Peak)

(.000008/.00002 Seconds)

(.0001 Seconds)

 

8-20 μs Microsecond

Up to 100 μs Microsecond

More than 100 μs Microsecond

480 RMS/678 Peak

2,400/3,394 Volts

1,680/2,376 Volts

622/880 Volts

77 RMS/392 Peak

1,387/1,958 Volts

970/1,371 Volts

360/509 Volts

240 Volts/339 Peak

1,202/1,700 Volts

840/1,188 Volts

311/440 Volts

120 Volts/170 Peak

601/850 Volts

356/593 Volts

156/220 Volts

 Nominal Voltage: Is the normal voltage rating of the SPD. Some common voltage examples are:

  1. 120/240 Volts Single Phase
  2. 120/208 Volts Three Phase
  3. 277/480 Volts Three Phase

MCOV Maximum Continuous Operating Voltage: The maximum designated root-mean-square (rms) value of the power frequency voltage that may be continuously applied to the mode of protection of an SPD.

Nominal Discharge Current (In): The manufacturer shall specify (declare) the value of the Nominal Discharge Current (In) to which the sample will be tested. The value of the Nominal Discharge Current (In) selected by the manufacturer shall be: 10 kA or 20 kA for Type 1 SPDs and 3 kA, 5 kA, 10 kA or 20 kA for Type 2 SPDs. With the SPD in the circuit the surge generator voltage shall be adjusted to ensure that the value of In (selected by the manufacturer) is impressed through the SPD. The resultant waveshape is permitted to deviate from the initial short circuit calibration of the 8 x 20 μs waveshape providing that the front time is a maximum of 9 μs and the duration is a minimum of 16 μs.

Per Mode Rating Defined: An SPDs per mode rating is based on the total amount of energy it can shunt from one circuit conductor to another. If an MOV capable of shunting a 50 kA of current is used in each pathway, then the per mode rating of the SPD is 50kA.

  1. The IEEE standard C62.41, states “a building's wiring adds impedance that will limit the surge current. The standard also states that 10kA devices have been adequately limiting surge currents at the service entrance for several years.
  2. Therefore, it is reasonable to say the largest surge that can enter a building's wiring system is 10kA; however, a direct lightning strike would produce a much larger surge.
  3. The only reason to have an Ac SPD per mode over 10kA is for a longer life of the Ac SPD.
    1. Technically speaking if a home or facility gets a lightning strike it may or may not end the life cycle of a 10kA per mode Ac SPD. Let us say a 250kA fer mode was installed it might tale 25 or more lightning strikes.

Ac SPD Response Time: UL, IEEE and IEC have not chosen to endorse response time as a valid Ac SPD rating parameter.

Coordinating Cascaded Ac SPDs: Coordinating cascaded is stepping down the Ac SPDs VPR and kA ratings downstream to the protected equipment. However, each Ac SPD should be a minimum of 30 wire feet from each other. Some SPD manufacturers recommend what they called “a 3, 2, 1 rule of thumb” for sizing SPD’s. 300kA rating for main panel, 200kA rating for distribution panel, and 100kA for final equipment panel.


Post a Comment

Comments

    Post A Comment

    « Back to Blog


    Safety Protection Grid Solutions

    P.O. Box 1366
    Mansfield, OH 44901
    (855) 887-8463

     

    Qualify Us Now! ProView

     

    International Association for Radio Telecommunication Electromagnetics Logo

    NARTE Certified Engineer Logo

     

     

    NFPA Member Logo

    InterNACHI Logo

     

    Copyright © 2024 SPGS America. All rights reserved.